Proline Promag 50W, 53W
4 Endress+Hauser
PROFIBUS PA interface:
• Transmission technology (Physical Layer): IEC 61158-2 (MBP), galvanically isolated
• Profile version 3.0
• Current consumption: 11 mA
• Permissible supply voltage: 9...32 V
• Bus connection with integrated reverse polarity protection
• Error current FDE (Fault Disconnection Electronic): 0 mA
• Function blocks: 1 x analog input, 1 x totalizer
• Output data: volume flow, totalizer
• Input data: positive zero return (ON/OFF), control totalizer, value for local display
• Cyclic data transmission compatible with previous model “Promag 33”
• Bus address adjustable via miniature switches or local display (optional) at the measuring device
Promag 53
Current output:
active/passive selectable, galvanically isolated, time constant selectable (0.01...100 s),
full scale value selectable, temperature coefficient: typically 0.005% o.r./°C (o.r. = of reading),
resolution: 0.5 µA
• active: 0/4…20 mA, R
L
< 700 Ω (HART: R
L
≥ 250 Ω)
• passive: 4…20 mA, operating voltage V
S
18...30 V DC, R
i
≤ 150 Ω
Pulse/frequency output:
active/passive selectable, galvanically isolated (Ex i version: only passive)
• active: 24 V DC, 25 mA (max. 250 mA during 20 ms), R
L
> 100 Ω
• passive: open collector, 30 V DC, 250 mA
• Frequency output: full scale frequency 2...10000 Hz (f
max
= 12500 Hz), EEx-ia: 2...5000 Hz;
on/off ratio 1:1; pulse width max. 10 s.
• Pulse output: pulse value and pulse polarity adjustable, pulse width configurable
(0.05...2000 ms)
PROFIBUS DP interface:
• Transmission technology (Physical Layer): RS485 in accordance with ANSI/TIA/EIA-485-A:
1998, galvanically isolated
• Profile version 3.0
• Data transmission rate: 9.6 kBaud...12 MBaud
• Automatic data transmission rate recognition
• Function blocks: 2 x analog input, 3 x totalizer
• Output data: volume flow, calculated mass flow, totalizer 1...3
• Input data: positive zero return (ON/OFF), totalizer control, value for local display
• Cyclic data transmission compatible with previous model “Promag 33”
• Bus address adjustable via miniature switches or local display (optional) at the measuring device
• Available output combination → Page 7 ff.
PROFIBUS PA interface:
• Transmission technology (Physical Layer): IEC 61158-2 (MBP), galvanically isolated
• Profile version 3.0
• Current consumption: 11 mA
• Permissible supply voltage: 9...32 V
• Bus connection with integrated reverse polarity protection
• Error current FDE (Fault Disconnection Electronic): 0 mA
• Function blocks: 2 x analog input, 3 x totalizer
• Output data: volume flow, calculated mass flow, totalizer 1...3
• Input data: positive zero return (ON/OFF), totalizer control, value for local display
• Cyclic data transmission compatible with previous model “Promag 33”
• Bus address adjustable via miniature switches or local display (optional) at the measuring device