5 Operation / adjusting device settings - Set-up to commissioning Memo-Graph S
52 Endress+Hauser
Interfaces: RS232 / RS422 / RS485 sub-menu
Settings only required if you use the device's interfaces (operation using PC, serial data readout,
modem operation, etc.).
Interfaces: Profibus DP sub-menu (option)
Settings only required if you are using PROFIBUS measuring points.
See also “Analogue inputs - Signal” and “Analogue inputs - PROFIBUS DP”
Set-up -> Interfaces -> RS232 / RS422 / RS485
Unit address Every device used in series must have its own address (00...99). This is required for identifying the PC software.
Baudrate The transmission rate (=“Baudrate”) must correspond to the PC software settings.
Parity This setting must correspond to the PC software settings.
Stop bits This setting must correspond to the PC software settings.
Data bits This setting must correspond to the PC software settings. Fixed - can not be changed.
Set-up -> Interfaces -> Profibus DP
Operating mode “Measured value monitor”: the (bus) measuring signals are requested by a higher-ranking (control) system.
Baudrate Baudrate for PROFIBUS DP, can not be changed.
Timeout If no measured value is received from the bus within the set time, bus operation is defective (or incorrect settings). The
device displays this with a message. In this case, no measured values can be registered.